OPTIM FRE: LV thyristor switched automatic capacitor banks with
Manufactured by Circutor

OPTIM FRE: LV thyristor switched automatic capacitor banks with

Automatic capacitor banks with rejection filters (static contactor), 50 Hz. 26 models, supplied across Saudi Arabia by Volt Solutions.

  • Use voltage (V): 440
  • 26 models available

Information

The Circutor OPTIM FRE series (LV thyristor switched automatic capacitor banks with) has 26 models. Ordering codes: R64E24, R64E25, R64E28, R64E29, R64E30, R64E32 and 20 more. Model names include OPTIM FRE4-150-440, OPTIM FRE4-175-440, OPTIM FRE4-200-440. Volt Solutions supplies it across Saudi Arabia.

The capacitor banks with detuned filters of the OPTIM FRE series have been designed for reactive energy correction in networks with fluctuating load levels, high harmonic presence and a risk of resonance.

The power variations are relatively quick (measured in milliseconds), and the operation is thus carried out by thyristors, which are connected to a voltage controller board, so that the connection and disconnection of the capacitor is carried out with zero voltage difference. Transients are prevented between the connection and disconnection of the steps, obtaining an immediate response to the load fluctuations.

Applications

The most common application is with individual loads or in installations where a quick compensation response is needed (e.g. welding units, motors for lifting units, lifts, etc.) and where the network has high harmonic content.

Specifications

Electrical characteristics
Voltage400 V (50 Hz) (other voltages on request)
Reinforcement voltage440 V
Surge10 % 8 h over 24 h 15 % up to 15 min over 24 hours 20 % up to 5 min over 24 hours 30 % up to 1 min over 24 hours
Discharge resistance75 V / 3 min
Tolerance C-5% / 10 %
Losses (W)< 0,5 W/kvar
Current measurement circuit
Permanent overload1,3 In
Transformation ratioIn / 5A
Environmental characteristics
Working temperatureTª class D: Daily average: 45 ºC, annual average: 35 ºC, maximum: 55 ºC, minimum: -50 ºC
Relative humidity (without condensation)80%
Protection classIP 21
Mechanical characteristics
EnvelopeSheet metal RAL 7035 Grey / RAL 3005 Garnet
FasteningVertical / Self-supporting
Thermal managementNatural or forced according to options
Protection
ElementProtection by stage by fuses with high cut-off power (APR). NH-00 series.
Features / performance
ComponentsCLZ capacitor Static switching unit on each stage, made up of static contactors (thyristors) Two-pole circuit breaker protection for capacitor bank and regulator operations. Reactive energy regulator of the Computer MAX-f Built-in thermostat on the heatsink for disconnecting the stage in the case of excessive temperatures (90 ºC) Detuned filters tuned to 189 Hz for protection against harmonics present in the network and for preventing resonance with harmonics of the 5th order or higher.
OptionalManual switch on capacitor bank header Circuit breaker on capacitor bank header Circuit breaker + earth leakage protection on capacitor bank header Forced ventilation unit + thermostat Polycarbonate sheet for protection against direct contacts 400/230 V autotransformer
Standards
StandardsUNE-EN 61921, UNE-EN 61439-1, UNE EN 60831
Electrical safety, Maximum height (m)2000 m

Models and codes

CodeModel Cable section (mm2)Stepskvar (400 V)kvar (440 V)Optional circuit breaker (A)Optional manual switch (A) Quote
R64E24 OPTIM FRE4-150-440 953125150400400 Get quote
R64E25 OPTIM FRE4-175-440 1203145175400400 Get quote
R64E28 OPTIM FRE4-200-440 1503165200400400 Get quote
R64E29 OPTIM FRE4-250-440 1853207250630630 Get quote
R64E30 OPTIM FRE4-300-440 2404248300630630 Get quote
R64E32 OPTIM FRE4-350-440 2×1504289350630630 Get quote
R64E34 OPTIM FRE4-400-440 2×1854331400800800 Get quote
R64J25 OPTIM FRE6-400-440 2×1855331400800800 Get quote
R64J30 OPTIM FRE6-450-440 2×1855372450800800 Get quote
R64J35 OPTIM FRE6-500-440 2×240541350010001000 Get quote
R64J40 OPTIM FRE6-550-440 2×240645555010001000 Get quote
R64J45 OPTIM FRE6-600-440 2×240649660010001000 Get quote
R64K36 OPTIM FRE8-600-440 2×240749660012501250 Get quote
R64K38 OPTIM FRE8-650-440 3×150753765012501250 Get quote
R64K40 OPTIM FRE8-700-440 3×150757970012501250 Get quote
R64K42 OPTIM FRE8-750-440 3×185862075016001600 Get quote
R64K44 OPTIM FRE8-800-440 3×185866180016001600 Get quote
R64C25 OPTIM FRE10-800-440 2×240 / 24086618001000+4001000+400 Get quote
R64C30 OPTIM FRE10-850-440 2×240 / 24097028501000+6301000+630 Get quote
R64C35 OPTIM FRE10-900-440 2×240 / 24097449001000+6301000+630 Get quote
R64C40 OPTIM FRE10-950-440 2×240 / 2×185107859501000+8001000+800 Get quote
R64C45 OPTIM FRE10-1000-440 2×240 / 2×1851082610001000+8001000+800 Get quote
R64L50 OPTIM FRE12-1050-440 2×240 / 2×2401186810501000+10001000+1000 Get quote
R64L55 OPTIM FRE12-1100-440 2×240 / 2×2401190911001000+10001000+1000 Get quote
R64L60 OPTIM FRE12-1150-440 2×240 / 2×2401295011502×10002×1000 Get quote
R64L65 OPTIM FRE12-1200-440 2×240 / 2×2401299212002×10002×1000 Get quote

Downloads