LRZ / LRBZ: Filter reactors for power converters (network side), 50 Hz
Manufactured by Circutor

LRZ / LRBZ: Filter reactors for power converters (network side), 50 Hz

Filter reactors for power converters (network side), 50 Hz. 7 models, supplied across Saudi Arabia by Volt Solutions.

  • 7 models available

Information

The Circutor LRZ / LRBZ series (filter reactors for power converters (network side), 50 Hz) has 7 models. Ordering codes: P73309, P7330B, P7330E, P7330G, P7330J, P7330K and 1 more. Model names include LRZ 04-033, LRZ 04-050, LRBZ 04-080. Volt Solutions supplies it across Saudi Arabia.

The motor speed regulation equipment, frequency variators, UPS units, etc. generate alterations in the network, which affect other loads in the installation of the operation of the equipment.
The LRZ / LRBZ reactors connected to the input on the network side of the equipment can attenuate voltage peaks and reduce the harmonic distortion generated by the power electronics. The LRZ / LRBZReactors for filtering can reduce the current harmonics in any converter from 40… 50 % to values around 20 %. In addition, they reduce the shortcircuit current and increase the safety of the converter’s semi-conductors. When installed on the motor side, they can attenuate harmonic frequencies caused during switching operations.

  • Low-powered reactors, LRZ type, are built with plates with low losses and are coiled with copper wire. The connection is achieved with the adequate terminals.
  • In the case of higher currents, LRBZ reactors are used, with a magnetic plate nucleus and multiple steel cores, which offer excellent characteristics and a low loss ratio. Copper band coils (or aluminium band, on demand). The connections run through a plate.
  • Both LRZ and LRBZ type reactors have a vacuum varnish sealing to increase the insulation, providing a greater mechanical resistance and reduce the level of noise.

Applications

The reactors of the LR / LRB series are prepared and can be used on the network and motor sides. They attenuate micro-drops and peaks during the initial connection and switching operations, and they reduce the rate of harmonics from the network current.

Specifications

Electrical characteristics
Voltageup to 1000 V~
Insulation voltage, circuit4 kV
Linearity (5% L)1,5 In
Maximum transient current2 In (1 min)
Current measurement circuit
Nominal current (In)According to table. Other values on request
Allowable overload1,7 In
Permanent overload1,7 In
Environmental characteristics
Thermal Class"class F (+155 ºC) On request: class H (+180 ºC)"
Protection classIP 00
Standards
StandardsUNE-EN 60289 , IEC 60076

Models and codes

CodeModel L(mH)In (A)LossesMotor P.Motor P. (CV) Quote
P73309 LRZ 04-033 0,9832451520 Get quote
P7330B LRZ 04-050 0,6747642230 Get quote
P7330E LRBZ 04-080 0,4761103750 Get quote
P7330G LRBZ 04-115 0,281101455575 Get quote
P7330J LRBZ 04-185 0,1718023090122 Get quote
P7330K LRBZ 04-200 0,15200245110150 Get quote
P7330M LRBZ 04-300 0,1300355160220 Get quote

Downloads

We send the manufacturer datasheet, manual and drawings for the exact model you need. Request the datasheet