STQ: Current transformers, split core
Current transformers, split core. 16 models, supplied across Saudi Arabia by Volt Solutions.
- System: Single-phase
- Transformer type: Split core
- Class 3 Power (VA): 1, 0,1
- Input current: 100 A, 150 A, 200 A, 250 A, 300 A, 50 A
- Class 1 Power (VA): 1, 0,1
- 16 models available
Information
The Circutor STQ series (current transformers, split core) has 16 models. Ordering codes: M73715, M73717, M73718, M73719, M7371A, M737150010000 and 10 more. Model names include STQ-24 100/5A, STQ-24 150/5A, STQ-24 200/5A. Volt Solutions supplies it across Saudi Arabia.
Open-core current transformers with compact dimensions for easy installation. This type of transformer is very easy to install and uninstall on compact panels where the reduced space makes it difficult to take current measurements. In addition, their open-core design means that they can take measurements without having to interrupt the electric supply. The primary current measurement range is from 100 A to 300 A using different secondary outputs (…/1A, …/5A or …/250mA) with a maximum admissible cable diameter of 24 mm.
Applications
Quick and easy assembly are a fundamental aspect when taking temporary measurements in an electrical installation. STQ-24 transformers can take energy measurements together with CIRCUTOR‘s power analyzers or energy meters (CVM-MINI, CVM-NET, CVM-C, CVM-B, EDMk, etc.) without having to interrupt the electric supply. The open-core design of the transformer makes it very easy to install and allows installers to take electrical measurements in less time.
Specifications
| Insulation voltage between terminals S1-S2 | 3 kV |
|---|---|
| Safety factor (SF) | 5 |
| Allowable overload | 1,2 In |
|---|---|
| Nominal frequency | 50 / 60 Hz |
| Dynamic current (Idyn) | 2,5 Ith |
| Thermal short-circuit current (Ith) | 60 In |
| Operating voltage | 0,72 kV~ máx. |
|---|---|
| Inner diameter Ø (mm) | 24 |
| Accuracy | Clase 1/3 |
|---|
| Working temperature | -5 … +40 ºC |
|---|---|
| Storage temperature | -20 … 75 ºC |
| Thermal Class | Class B (+130 ºC) |
| Relative humidity (without condensation) | 15 … 85% |
| Protection class | IP 20 |
| Envelope | PC LexanTM 940-701 |
|---|---|
| Size (mm) width x height x depth | 53 x 70 x 43.2 (mm) |
| Standards | UNE-EN 61869-1, UNE-EN 61869-2 |
|---|---|
| Electrical safety, Maximum height (m) | 1000 |
Models and codes
| Code | Model | Class 3 Power (VA) | Measurement Range (A) | Input current | Class 1 Power (VA) | Quote |
|---|---|---|---|---|---|---|
| M73715 | STQ-24 100/5A | 1 | 100/5 | 100 A | – | Get quote |
| M73717 | STQ-24 150/5A | 1 | 150/5 | 150 A | – | Get quote |
| M73718 | STQ-24 200/5A | 1 | 200/5 | 200 A | – | Get quote |
| M73719 | STQ-24 250/5A | – | 250/5 | 250 A | 1 | Get quote |
| M7371A | STQ-24 300/5A | – | 300/5 | 300 A | 1 | Get quote |
| M737150010000 | STQ-24 100/1A | 1 | 100/1 | 100 A | – | Get quote |
| M737170010000 | STQ-24 150/1A | 1 | 150/1 | 150 A | – | Get quote |
| M737180010000 | STQ-24 200/1A | 1 | 200/1 | 200 A | – | Get quote |
| M737190010000 | STQ-24 250/1A | – | 250/1 | 250 A | 1 | Get quote |
| M7371A0010000 | STQ-24 300/1A | – | 300/1 | 300 A | 1 | Get quote |
| M7371200A0000 | STQ-24 50/250 mA | 0,1 | 50/250 mA | 50 A | – | Get quote |
| M7371500A0000 | STQ-24 100/250 mA | 0,1 | 100/250 mA | 100 A | – | Get quote |
| M7371700A0000 | STQ-24 150/250 mA | 0,1 | 150/250 mA | 150 A | – | Get quote |
| M7371800A0000 | STQ-24 200/250 mA | 0,1 | 200/250 mA | 200 A | – | Get quote |
| M7371900A0000 | STQ-24 250/250 mA | – | 250/250 mA | 250 A | 0,1 | Get quote |
| M7371A00A0000 | STQ-24 300/250 mA | – | 300/250 mA | 300 A | 0,1 | Get quote |