DHC-96 CPM: Digital instruments: Programmable DC measurement Central
Digital instruments: Programmable DC measurement Central. 1 model, supplied across Saudi Arabia by Volt Solutions.
- Protocol: Modbus RTU
- IP: 54
- Communications: RS-485
- Relays: 2
- Digital inputs: 2
- Analog output: 1 (20 mA)
- System: DC (Shunt)
- Measurement Range (V): ± 150 / 300 /600 / 1000 / 1500 Vdc
Information
The Circutor DHC-96 CPM series (digital instruments: Programmable DC measurement Central) has 1 model. Ordering code: M223C8. Volt Solutions supplies it across Saudi Arabia.
Panel-mounted digital instruments that display the value of an electrical variable measured or proportional value of a process signal on its screen (depending on the model). Designed to supervise, regulate and control units with the use of relay outputs that are built in the unit.
The DHC-96 series displays the value of an electrical variable measured or proportional value of a process signal on its screen (depending on the model). The unit displays the electrical parameters of a single-phase installation, depending on the model, such as the voltage, current, etc. In DC systems, the unit can measure the voltage, current, frequency and other variables associated with industrial processes. The AC models take the measurements in true RMS (TRMS).
All models in this range have the following features:
- Universal power supply at 80…270 Vac/dc (DHC-96-CPM: 100…270 Vac/dc) and optional power supply at 16 … 36 Vdc (DHC-96-CPM: 20…60 Vdc)
- IP 54 protection degree on the front panel
- High measurement accuracy
- Programmable measuring input
- Alarm delays and interlockings
- Galvanic insulation between external circuits
- Self-configurable decimal point
- Installed on 96 x 49 mm panels
Applications
These digital instruments have many different applications and can be used in:
- Industrial applications
- Air conditioning units
- Solar photovoltaic energy installations
- Industrial process control systems
Specifications
| Nominal voltage | 100…270 V ~ |
|---|---|
| Frequency | 50/60 Hz |
| Consumption | 6 … 18 VA |
| Installation category | CAT III 300V |
| Nominal voltage | 100…270 Vdc |
|---|---|
| Consumption | 1.3 … 2 W |
| Installation category | CAT III 300 V |
| Nominal voltage | ± 150 / 300 / 600 / 1000 / 1500 Vdc |
|---|---|
| Input impedance | > 1 MΩ |
| Maximum permanent measurement voltage | 1.2 Un continuous |
| Consumption | < 1 VA |
| Installation category | CAT III 1500 V |
| Nominal current (In) | Shunt: 50 / 60 /75 / 100 / 150 / 200 / 250 / 300 / 400 / 600 mV |
|---|---|
| Allowable overload | 1.2 In continuous |
| Consumption | < 1 VA |
| Installation category | CAT III 1500 V |
| Phase voltage measurement | Class 0.5 |
|---|---|
| Phase current measurement | Class 0.5 |
| Active power measurement (kW) | Class 1 |
| Active energy measurement (kWh) | Class 1 |
| Quantity | 2 |
|---|---|
| Maximum current | 2.5 A |
| Electrical life | 1 x 10 5 |
| Maximum switching capacity | 625 VA |
| Quantity | 2 |
|---|---|
| Type | Potential-free contact |
| Input/output insulation | 2000 V ~ |
| Maximum short-circuit current | 3.3 mA dc |
| Maximum open circuit voltage | 17 V dc |
| Quantity | 1 |
|---|---|
| Maximum internal voltage | 17 V dc |
| Linearity | 0.5 % |
| Current mode, nominal range | 0 … 20 mA, 4 … 20 mA, 4-12-20 mA |
| Current mode: maximum load resistance | 350 Ω |
| Technology / Type | RS-485 |
|---|---|
| Protocol | ModBus RTU |
| Display type | LCD 5 digits |
|---|---|
| Keyboard | 4 keys |
| Working temperature | -25 … +55 ºC |
|---|---|
| Storage temperature | -25 … +70 ºC |
| Relative humidity (without condensation) | ≤ 93 % |
| Protection class | Front: IP54, Rear case: IP20 |
| Standards | IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61010-1, IEC 61326-1 |
|---|---|
| Electrical safety, Installation category | CAT III 300 V |
| Electrical safety, Maximum height (m) | 2000 |
| Weight (kg) | 0,268 |
|---|---|
| Size (mm) width x height x depth | 96 x 49 x 107.7 (mm) |
Models and codes
| Code | Model | Protocol | IP | Communications | Relays | Quote |
|---|---|---|---|---|---|---|
| M223C8 | DHC-96 CPM 1500 | Modbus RTU | 54 | RS-485 | 2 | Get quote |