DHC-96: Digital instruments 96 x 48 with analogue output
Digital instruments 96 x 48 with analogue output. 6 models, supplied across Saudi Arabia by Volt Solutions.
- 6 models available
Information
The Circutor DHC-96 series (digital instruments 96 x 48 with analogue output) has 6 models. Ordering codes: M22318, M22388, M22338, M22348, M22358, M22368. Model names include DHC-96 Vac, DHC-96 Vdc, DHC-96 HVdc. Volt Solutions supplies it across Saudi Arabia.
Panel-mounted digital instruments that display the value of an electrical variable measured or proportional value of a process signal on its screen (depending on the model). Designed to supervise, regulate and control units with the use of relay outputs that are built in the unit.
The DHC-96 series displays the value of an electrical variable measured or proportional value of a process signal on its screen (depending on the model). The unit displays the electrical parameters of a single-phase installation, depending on the model, such as the voltage, current, etc. In DC systems, the unit can measure the voltage, current, frequency and other variables associated with industrial processes. The AC models take the measurements in true RMS (TRMS).
All models in this range have the following features:
- Universal power supply at 80…270 Vac/dc (DHC-96-CPM: 100…270 Vac/dc) and optional power supply at 16 … 36 Vdc (DHC-96-CPM: 20…60 Vdc)
- IP 54 protection degree on the front panel
- High measurement accuracy
- Programmable measuring input
- Alarm delays and interlockings
- Galvanic insulation between external circuits
- Self-configurable decimal point
- Installed on 96 x 49 mm panels
Applications
These digital instruments have many different applications and can be used in:
- Industrial applications
- Air conditioning units
- Solar photovoltaic energy installations
- Industrial process control systems
Specifications
| Nominal voltage | 80…270 V ~ |
|---|---|
| Frequency | 50/60 Hz |
| Installation category | CAT III 300V |
| Nominal voltage | 80…270 Vdc |
|---|---|
| Installation category | CAT III 300 V |
| Quantity | 2 |
|---|---|
| Maximum open contact voltage | 277 V ~ |
| Maximum current | 5 A ~ |
| Resistive load (max.) | 250 Vca / 5 Aca, 30 Vcc / 5 Acc |
| Electrical life | 1 x 10 5 |
| Maximum switching capacity | 1385 VA |
| Quantity | 2 |
|---|---|
| Type | Potential-free contact |
| Input/output insulation | 2000 V ~ |
| Maximum short-circuit current | 3.3 mA dc |
| Quantity | 1 |
|---|---|
| Maximum internal voltage | 17 V dc |
| Linearity | 0.5 % |
| Current mode, nominal range | 0 … 20 mA, 4 … 20 mA, 4-12-20 mA |
| Current mode: maximum load resistance | 350 Ω |
| Technology / Type | RS-485 |
|---|---|
| Protocol | ModBus RTU |
| Display type | LCD 5 digits |
|---|---|
| Keyboard | 4 keys |
| Working temperature | -40 … +70 ºC |
|---|---|
| Storage temperature | -40 … +85 ºC |
| Relative humidity (without condensation) | ≤ 95 % |
| Envelope | Polycarbonate + ABS |
|---|---|
| Weight (kg) | 0,2 |
| Size (mm) width x height x depth | 96 x 49 x 89.2 (mm) |
| Standards | IEC 61010-1, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11 |
|---|---|
| Electrical safety, Installation category | CAT III 300 V |
| Electrical safety, Maximum height (m) | 2000 |
Models and codes
| Code | Model | Protocol | Scale | IP | Communications | Relays | Digital inputs | Quote |
|---|---|---|---|---|---|---|---|---|
| M22318 | DHC-96 Vac | Modbus RTU | 63,5 V / 100 V / 110 V /230 V /380 V /480 V | 54 | RS-485 | 2 | 2 | Get quote |
| M22388 | DHC-96 Vdc | – | – | – | – | – | – | Get quote |
| M22338 | DHC-96 HVdc | Modbus RTU | ± 1500 V | 54 | RS-485 | 2 | 2 | Get quote |
| M22348 | DHC-96 mVdc | Modbus RTU | 60 mV / 75 mV / 100 mV / 150 mV / 200 mV | 54 | RS-485 | 2 | 2 | Get quote |
| M22358 | DHC-96 Aac | Modbus RTU | 1 A~ / 5 A~ | 54 | RS-485 | 2 | 2 | Get quote |
| M22368 | DHC-96 mAdc | Modbus RTU | -20 … +20 mA / 0…20 mA / 4…20 mA | 54 | RS-485 | 2 | 2 | Get quote |