DHC-96: Digital instruments 96 x 48 with analogue output
Manufactured by Circutor

DHC-96: Digital instruments 96 x 48 with analogue output

Digital instruments 96 x 48 with analogue output. 6 models, supplied across Saudi Arabia by Volt Solutions.

  • 6 models available

Information

The Circutor DHC-96 series (digital instruments 96 x 48 with analogue output) has 6 models. Ordering codes: M22318, M22388, M22338, M22348, M22358, M22368. Model names include DHC-96 Vac, DHC-96 Vdc, DHC-96 HVdc. Volt Solutions supplies it across Saudi Arabia.

Panel-mounted digital instruments that display the value of an electrical variable measured or proportional value of a process signal on its screen (depending on the model). Designed to supervise, regulate and control units with the use of relay outputs that are built in the unit.

The DHC-96 series displays the value of an electrical variable measured or proportional value of a process signal on its screen (depending on the model). The unit displays the electrical parameters of a single-phase installation, depending on the model, such as the voltage, current, etc. In DC systems, the unit can measure the voltage, current, frequency and other variables associated with industrial processes. The AC models take the measurements in true RMS (TRMS).

All models in this range have the following features:

  • Universal power supply at 80…270 Vac/dc (DHC-96-CPM: 100…270 Vac/dc) and optional power supply at 16 … 36 Vdc (DHC-96-CPM: 20…60 Vdc)
  • IP 54 protection degree on the front panel
  • High measurement accuracy
  • Programmable measuring input
  • Alarm delays and interlockings
  • Galvanic insulation between external circuits
  • Self-configurable decimal point
  • Installed on 96 x 49 mm panels

Applications

These digital instruments have many different applications and can be used in:

  • Industrial applications
  • Air conditioning units
  • Solar photovoltaic energy installations
  • Industrial process control systems

Specifications

AC power supply
Nominal voltage80…270 V ~
Frequency50/60 Hz
Installation categoryCAT III 300V
DC power supply
Nominal voltage80…270 Vdc
Installation categoryCAT III 300 V
Digital relay outputs
Quantity2
Maximum open contact voltage277 V ~
Maximum current5 A ~
Resistive load (max.)250 Vca / 5 Aca, 30 Vcc / 5 Acc
Electrical life1 x 10 5
Maximum switching capacity1385 VA
Digital inputs
Quantity2
TypePotential-free contact
Input/output insulation2000 V ~
Maximum short-circuit current3.3 mA dc
Analogue outputs
Quantity1
Maximum internal voltage17 V dc
Linearity0.5 %
Current mode, nominal range0 … 20 mA, 4 … 20 mA, 4-12-20 mA
Current mode: maximum load resistance350 Ω
Serial communication
Technology / TypeRS-485
ProtocolModBus RTU
User interface
Display typeLCD 5 digits
Keyboard4 keys
Environmental characteristics
Working temperature-40 … +70 ºC
Storage temperature-40 … +85 ºC
Relative humidity (without condensation)≤ 95 %
Mechanical characteristics
EnvelopePolycarbonate + ABS
Weight (kg)0,2
Size (mm) width x height x depth96 x 49 x 89.2 (mm)
Standards
StandardsIEC 61010-1, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11
Electrical safety, Installation categoryCAT III 300 V
Electrical safety, Maximum height (m)2000

Models and codes

CodeModel ProtocolScaleIPCommunicationsRelaysDigital inputs Quote
M22318 DHC-96 Vac Modbus RTU63,5 V / 100 V / 110 V /230 V /380 V /480 V54RS-48522 Get quote
M22388 DHC-96 Vdc –––––– Get quote
M22338 DHC-96 HVdc Modbus RTU± 1500 V54RS-48522 Get quote
M22348 DHC-96 mVdc Modbus RTU60 mV / 75 mV / 100 mV / 150 mV / 200 mV54RS-48522 Get quote
M22358 DHC-96 Aac Modbus RTU1 A~ / 5 A~54RS-48522 Get quote
M22368 DHC-96 mAdc Modbus RTU-20 … +20 mA / 0…20 mA / 4…20 mA54RS-48522 Get quote

Downloads