Manufactured by Circutor
CC: Current transducer
Current transducer. 4 models, supplied across Saudi Arabia by Volt Solutions.
- Output type: 1, 2, 1, 3
- Analog output: 0…20mA, 4…20mA
- Measure: 5 Aac, 20 mA
- Parameter: A ~, A dc
- 4 models available
Information
The Circutor CC series (current transducer) has 4 models. Ordering codes: M25131, M25132, M25161, M25162. Model names include CC-A Out1, CC-A Out2, CC-D Out1. Volt Solutions supplies it across Saudi Arabia.
CC-A transducers, convert A.C current to D.C process indicator signal.
The analog output is directly proportional to the input signal, calibrated as a RMS with sinus signal of 50 Hz.
Specifications
| Frequency | 40…90 Hz |
|---|---|
| Consumption | 2,5 VA |
| Allowable overload | 300 % In permanent |
|---|
| Phase current measurement | 0,2 % FS |
|---|
| Displaced output | 0,2…2 V / 2…10 V / 4…20 mA |
|---|---|
| Voltage mode: nominal output range | 0…5, 10 Vac |
| Load impedance in voltage | > 500 Ω |
|---|---|
| Load impedance in current | < 500 Ω |
| Response time | < 300 ms (0…99 % Vn) |
| Ripple (effective RMS value) | < 0,5 % |
| Working temperature | -10…+55 °C |
|---|---|
| Storage temperature | -40….+70 °C |
| Protection class | IP 20 (Terminals) IP 40 (case) |
| Standards | IEC 529, IEC 688, IEC 801, EN 50081-2, EN 50082-2, IEC 1010 |
|---|---|
| Electrical safety, Maximum height (m) | 2000 |
| Size (mm) width x height x depth | 45 x 75 x 110 (mm) |
|---|