Manufactured by Circutor
CW / CY: Power transducer
Power transducer. 3 models, supplied across Saudi Arabia by Volt Solutions.
- Output type: 2
- Analog output: 4…20mA
- System: Single-phase, Unbalanaced three-phase ARON (3 wires)
- Parameter: kW, kvar
- 3 models available
Information
The Circutor CW / CY series (power transducer) has 3 models. Ordering codes: M25212, M25232, M25252. Model names include CW-M Out2, CW-TA Out2, CY-M Out2. Volt Solutions supplies it across Saudi Arabia.
The CW transducers, convert the signal measured to D.C. signal process.
The analog output is directly proportional to active power – single phase measurement. The measurement is in true RMS.
Specifications
| Nominal voltage | 24/115/230/400 Vca (-15…+20 %) |
|---|---|
| Frequency | 40…90 Hz |
| Consumption | 3 VA |
| Test voltage (kV) | 3 kV RMS 50 Hz 1min |
|---|---|
| Pulse test (kV) | 4 kV (1,2/50µs) |
| Nominal voltage | 0…660 Vca |
|---|---|
| Voltage measuring range | 0…150 % Vn |
| Frequency measuring range | 45…65 Hz |
| Input impedance | 3000 Ω/V |
| Maximum permanent measurement voltage | 1000 V |
| Nominal current (In) | 1 A / 5 A |
|---|---|
| Phase current measurement | 0…150 % In |
| Allowable overload | 300 % In permanent |
| Consumption | 0,2 VA |
| Phase current measurement | 0,5 % FS |
|---|
| Displaced output | 0,2…2 V / 2…10 V / 4…20 mA |
|---|---|
| Voltage mode: nominal output range | 0…5, 10 Vac |
| Load impedance in voltage | > 500 Ω |
|---|---|
| Load impedance in current | < 500 Ω |
| Response time | < 300 ms (0…99 % Vn) |
| Ripple (effective RMS value) | < 0,5 % |
| Working temperature | -10…+55 °C |
|---|---|
| Storage temperature | -40….+70 °C |
| Protection class | IP 20 (Terminals) IP 40 (case) |
| Standards | IEC 529, IEC 688, IEC 801, EN 50081-2, EN 50082-2, IEC 1010 |
|---|---|
| Electrical safety, Maximum height (m) | 2000 |
| Weight (kg) | 0,54 |
|---|---|
| Size (mm) width x height x depth | 95 x 72 x 110 (mm) |