FLEX-R: Flexible sensors for MYeBOX analysers
Flexible sensors for MYeBOX analysers. 3 models, supplied across Saudi Arabia by Volt Solutions.
- Nr Sensors: 1
- Measurement Range (A): 10 … 100 A / 100 … 1000 A / 1000 … 10000 A
- IΔn min.(A): 1
- I min: 1, 10, 500
- Lenght: 45 cm, 80 cm, 120 cm
- Usefull diam.(mm): 140, 250, 380
- 3 models available
Information
The Circutor FLEX-R series (flexible sensors for MYeBOX analysers) has 3 models. Ordering codes: M81611, M81612, M81613. Model names include KIT 1 -FLEX-R45, KIT 1-FLEX-R80, KIT 1-FLEX-R120. Volt Solutions supplies it across Saudi Arabia.
The flexible current sensor can take alternating current measurements from any installation with a full rejection of DC components, a very low consumption of power, with no saturation problems, a low temperature dependence and a very good linearity. The flexible sensor has been designed according to the Rogowsky coil principle, measuring alternating current irrespective of the position of the conductor. The current conductor must not be near the coil cable joint, since the degree of error increases in this area. Its centred location also reduces the impact of external magnetic fields. Thanks to the flexibility of the current sensor, one or more conductors can be surrounded, regardless of their shape, to perform current measurement actions.
Applications
These flexible current sensors have been specially designed for the MYeBOX-150 and MYeBOX-1500 portable power analysers.
Specifications
| Nominal frequency | 50Hz/60 Hz. |
|---|
| Linearity | (10…100%) ± 0,2 % |
|---|---|
| Accuracy | ± 1 % |
| Output voltage | 76 µV/A a 50 Hz |
| Maximum temperature coefficient | ± 0,05 % |
| Position sensitivity (cable connection) | ± 3 % |
| External fields | ± 2 % |
| Working temperature | -20…85 °C |
|---|---|
| Storage temperature | -40…85 °C |
| Relative humidity (without condensation) | 15…85 % |
| Protection class | IP 20 / IP 54 with terminal cover (optional) (for models Ø 85, 100, 116 mm) |
| Envelope | sensor material: Self-extinguishing UNE 21031 90 °C / Material couplings: PA V-0 |
|---|
| Standards | Dielectric strength IEC 61010-2-32 ( 5,4 kV 50 Hz) |
|---|---|
| Electrical safety, Installation category | 1000V CAT III / 600V CAT IV |
| Electrical safety, Contamination level/class | Pollution resistance 2 |
| Insulation | Double-insulated electric shock protection class II (IEC 61010-1) |
|---|