FLEX-RMG: Flexible sensors for MYeBOX analysers
Manufactured by Circutor

FLEX-RMG: Flexible sensors for MYeBOX analysers

Flexible sensors for MYeBOX analysers. 2 models, supplied across Saudi Arabia by Volt Solutions.

  • Nr Sensors: 1
  • Measurement Range (A): 10 … 100 A / 100 … 1000 A / 1000 … 10000 A
  • I min: 1, 10, 500
  • Lenght: 22 cm, 38 cm
  • Usefull diam.(mm): 70, 120
  • 2 models available

Information

The Circutor FLEX-RMG series (flexible sensors for MYeBOX analysers) has 2 models. Ordering codes: M81911, M81912. Model names include kit 1 FLEX RMG70, kit 1 FLEX RMG120. Volt Solutions supplies it across Saudi Arabia.

The flexible current sensor can take alternating current measurements from any installation with a full rejection of DC components, a very low consumption of power, with no saturation problems, a low temperature dependence and a very good linearity. The flexible sensor has been designed according to the Rogowsky coil principle, measuring alternating current irrespective of the position of the conductor. The current conductor must not be near the coil cable joint, since the degree of error increases in this area. Its centred location also reduces the impact of external magnetic fields. Thanks to the flexibility of the current sensor, one or more conductors can be surrounded, regardless of their shape, to perform current measurement actions.

Applications

These flexible current sensors have been specially designed for the MYeBOX-150 and MYeBOX-1500 portable power analysers.

Specifications

Current measurement circuit
Nominal frequency50Hz/60 Hz.
Specific technical characteristics of current sensors
Linearity(10…100%) ± 0,2 %
Output voltage100 µV/A a 50 Hz
Maximum temperature coefficient± 0,05 %
Position sensitivity (cable connection)± 3 %
External fields± 2 %
Environmental characteristics
Working temperature-20…85 °C
Storage temperature-40…85 °C
Relative humidity (without condensation)15…85 %
Protection classIP 54
Mechanical characteristics
EnvelopeSensor material: Self-extinguishing UNE 21031 90 °C / Material couplings: PA V-0
Standards
StandardsDielectric strength IEC 61010-2-32 ( 5,4 kV 50 Hz), IEC 61010-1
Electrical safety, Contamination level/classPollution resistance 2
Electrical safety
InsulationDouble-insulated electric shock protection class II (IEC 61010-1)

Models and codes

CodeModel DescriptionLenghtUsefull diam.(mm) Quote
M81911 kit 1 FLEX RMG70 Flexible sensors22 cm70 Get quote
M81912 kit 1 FLEX RMG120 Flexible Clamp38 cm120 Get quote

Downloads

Support from our engineers

You may also be interested in