Computer PV12: Reactive energy regulator for photovoltaic applications
Reactive energy regulator for photovoltaic applications. 1 model, supplied across Saudi Arabia by Volt Solutions.
- Alarm relay: Yes
- Communications: RS-485
- Measurement Range (V): 20…300
- IΔn (A): yes
- Power supply: 100…520 Vac
- Steps: 12
- Input current: … /5 A, … /1 A.
- Switching unit: Contactor
Information
The Circutor Computer PV12 series (reactive energy regulator for photovoltaic applications) has 1 model. Ordering code: R13882. Volt Solutions supplies it across Saudi Arabia.
The Computer PV12 is a power factor controller designed for installations with photovoltaic self-consumption and for applications where it is necessary to sum currents from different energy sources.
The device measures the cos φ of the network and controls capacitor connection and disconnection to maintain it at the target value. Additionally, it calculates and displays the main electrical parameters in single-phase and balanced three-phase networks.
The measurement is carried out in true effective value (True RMS) through 4 AC voltage inputs, 3 independent current inputs, and 1 input for measuring leakage current.
The Computer PV12 range allows up to 3 independent energy source measurements and combines them into a total reading.
Applications
The connection with 1, 2, or 3 current transformers allows the Computer PV12 to sum the contributions of different energy sources, making it ideal for photovoltaic self-consumption installations where a conventional controller may struggle to correctly read and compensate the cos φ.
It is also suitable for installations requiring up to 4 cos φ targets, enabling the compensation to adapt to different needs, for instance across time slots.
Specifications
| Nominal voltage | 100 … 520 V ~ |
|---|---|
| Frequency | 50 … 60 Hz |
| Consumption | 13 … 20 VA |
| Installation category | CAT III 300 V |
| Nominal voltage | 230 V Ph-N, 400 V Ph-Ph |
|---|---|
| Voltage measuring range | 20…300 V Ph-N , 35…520 V Ph-Ph |
| Frequency measuring range | 45 … 65 Hz |
| Input impedance | 660 kΩ |
| Minimum measurement voltage (Vstart) | 20 V F-N, 35 V F-F |
| Installation category | CAT III 300 V |
| Sampling frequency | 45 … 65 Hz |
| Nominal current (In) | …/5A ó …/1A |
|---|---|
| Phase current measuring range | 1 … 120 % In |
| Minimum current measurement | 50 mA |
| Phase voltage measurement | 0.5% ± 1 digit |
|---|---|
| Phase current measurement | 0.5% ± 1 digit |
| Active power measurement (kW) | 0.5% ± 2 digits |
| Reactive power measurement (kvar) | 1% ± 2 digit |
| Active energy measurement (kWh) | Class 1 |
| Reactive energy measurement (kvarh) | Class 1 |
| Minimum current measurement (Istart) | 10 mA |
|---|---|
| Measurement range | 0,01 … 1,5 A |
| Type | NPN |
|---|---|
| Maximum current | 50 mA |
| Quantity | 14 (12 salidas, 1 ventilador, 1 alarma) |
|---|---|
| Maximum open contact voltage | 1 kV |
| Maximum current | 1A |
| Electrical life | 30 x 10 3 ciclos |
| Mechanical life | 5 x 10 6 Cycles |
| Maximum switching capacity | 2500 VA |
| Type | Potential-free contact |
|---|---|
| Input/output insulation | Optoisolated |
| Technology / Type | RS-485 |
|---|---|
| Protocol | Modbus RTU |
| Display type | LCD Custom COG |
|---|---|
| LED | 4 LED |
| Keyboard | Capacitive, 5 keys |
| Working temperature | -10 … +55 ºC |
|---|---|
| Storage temperature | -20 … +70 ºC |
| Relative humidity (without condensation) | 5 … 95% |
| Protection class | IP 51 (Front), IP 31 (unmounted) |
| Envelope | Plastic V0 self-extinguishing |
|---|---|
| Fastening | Panel |
| Weight (kg) | 0,6 |
| Size (mm) width x height x depth | 144 x 144 x 71 (mm) |
| Standards | IEC 61010, IEC 61000-6-2, IEC 61000-6-4, Medidas conforme a : IEC 61557-12 |
|---|---|
| Electrical safety, Maximum height (m) | 2000 |
Models and codes
| Code | Model | Alarm relay | Communications | Measurement Range (V) | IΔn (A) | Quote |
|---|---|---|---|---|---|---|
| R13882 | Computer PV 12 | Yes | RS-485 | 20…300 | yes | Get quote |