DIR: Power factor relay 1 step. DIN rail
Manufactured by Circutor

DIR: Power factor relay 1 step. DIN rail

Power factor relay 1 step. DIN rail. 1 model, supplied across Saudi Arabia by Volt Solutions.

  • Alarm relay: No
  • Power supply (Vac): 400 Vac
  • Steps: 1
  • Input current: …/250 mA
  • Switching unit: Contactor

Information

The Circutor DIR series (power factor relay 1 step. DIN rail) has 1 model. Ordering code: R11211. Volt Solutions supplies it across Saudi Arabia.

The DIR2 Power Factor Relay is capable of acting on a circuit in accordance with the reactive inductive or capacitive current transmitted through it. The DIR2 relay measures reactive current in mA of the secondary of a …/250 mA current transformer MC1 or MC3 type. The front of the relay has a control panel that is used to adjust the reactive current where the relay will act. It has a LED that indicates the status of the relay.

Applications

The DIR2 relay is easy to install and program, making it the best solution in the following applications:

  • Individual compensation of small, medium or large power loads.
  • Partial compensation in installations with automatic equipment available.
  • Partial or total regulator in low-power installations.Instantaneous and total disconnection of capacitor banks when there is a high capacitive current in the network.
  • Control of reactive currents- capacitive and inductive – triggering an alarm signal when a high current is detected.

Specifications

AC power supply
Nominal voltage400 V ~ ±10%
Frequency50-60 Hz
Consumption< 3 VA
Current measurement circuit
Nominal current (In)0,25 A ~
Allowable overload1,2 In
Consumption< 0,05 VA
Permanent overload1,2 In
Idle current tripping
C/K trip adjustment range0,15 … 2
Connection delay Tc5 s
Disconnection delay Tr2 s
Digital relay outputs
Thermal current (Ith)10 A
DC11 Ie/Ue0,3 A / 110 V dc
AC11 Ie/Ue10 A / 250 V ~
Electrical life10×10 4 maniobras
Mechanical life10×10 6 operations
Environmental characteristics
Working temperature-10 … +50 ºC
Relative humidity (without condensation)95%
Protection classIP 40
Standards
StandardsEN 61010, EN 61000-3-2, EN 61000-3-3, EN 50081-2, EN 50082-1, EN 50082-2, EN 61000-4-2, EN 61000-4-4, EN 61000-4-8, EN 61000-4-5, EN 61000-4-11, UL 94
CertificationsUL
Electrical safety, Maximum height (m)2000
Electrical safety
InsulationDouble-insulated electric shock protection class II (IEC 61010-1)
Mechanical characteristics
Weight (kg)0,1
Size (mm) width x height x depth35 x 85 x 73 (mm)

Models and codes

CodeModel Alarm relayPower supply (Vac)StepsInput current Quote
R11211 DIR2 No400 Vac1…/250 mA Get quote

Downloads