computer SMART III: Power factor controllers
Three-phase Power factor controllers. Regulation, measurement, leakage control and communications. 7 models, supplied across Saudi Arabia by Volt Solutions.
- Alarm relay: Yes
- Communications: RS-485
- IΔn (A): yes
- Input current: …/5A, …/1A
- Measurement Range (V): 20…300, 100…520
- Power supply (Vac): 100…520 Vac, 100…400 Vac
- 7 models available
Information
The Circutor computer SMART III series (power factor controllers) has 7 models. Ordering codes: R13851, R13862, R13864, R13953, R13964, R13951 and 1 more. Model names include computer SMART III 6, computer SMART III 12, computer SMART III 14. Volt Solutions supplies it across Saudi Arabia.
Measurement with three current transformers guarantees an analogue reading of the company meter. The Computer SMART III reactive energy regulator is the only regulator on the market that offers the possibility of using 3 measurement transformers in addition to the conventional method of measuring with a single current transformer, as well as providing the functions of an integral power analyzer and controlling residual leakage currents (WG series current transformers).
Computer SMART III is a regulator that ensures excellent preventive maintenance by means of programming its alarms and the options for testing the capacitor status, offering maximum supervision and safety of your compensation unit.
Applications
The connection of 1 or 3 transformers makes Computer SMART III the perfect regulator in any installation, allowing the following:
- Changing from 1 to 3 transformers in the following cases:
- Changes in reactive energy penalties
- Changes in consumption habits
- Significant imbalances in the system
- Replacing the regulator of any capacitor bank
- Perfect for installations with up to 4 objective cos φ, since it can adapt to any compensation need (different time periods).
- It can be used with Medium Voltage compensation units.
Specifications
| Nominal voltage | 100 … 520 V ~ |
|---|---|
| Frequency | 50 … 60 Hz |
| Installation category | CAT III 300 V |
| Nominal voltage | 230 V Ph-N, 400 V Ph-Ph |
|---|---|
| Voltage measuring range | 20…300 V Ph-N , 35…520 V Ph-Ph |
| Frequency measuring range | 45 … 65 Hz |
| Input impedance | 660 kΩ |
| Minimum measurement voltage (Vstart) | 20 V F-N, 35 V F-F |
| Installation category | CAT III 300 V |
| Sampling frequency | 45 … 65 Hz |
| Nominal current (In) | …/5A ó …/1A |
|---|---|
| Phase current measuring range | 1 … 120 % In |
| Minimum current measurement | 50 mA |
| Phase voltage measurement | 0.5% ± 1 digit |
|---|---|
| Phase current measurement | 0.5% ± 1 digit |
| Active power measurement (kW) | 0.5% ± 2 digits |
| Reactive power measurement (kvar) | 1% ± 2 digit |
| Active energy measurement (kWh) | Class 1 |
| Reactive energy measurement (kvarh) | Class 1 |
| Minimum current measurement (Istart) | 10 mA |
|---|---|
| Measurement range | 0,01 … 1,5 A |
| Secondary nominal current | 0,003 A |
| Maximum voltage | 24 Vcc |
|---|
| Maximum open contact voltage | 1 kV |
|---|---|
| Maximum current | 1A |
| Electrical life | 30 x 10 3 ciclos |
| Mechanical life | 5 x 10 6 Cycles |
| Maximum switching capacity | 2500 VA |
| Quantity | 2 |
|---|---|
| Type | Potential-free contact |
| Input/output insulation | Optoisolated |
| Technology / Type | RS-485 |
|---|---|
| Protocol | Modbus RTU |
| Display type | LCD Custom COG |
|---|---|
| LED | 4 LED |
| Keyboard | Capacitive, 5 keys |
| Working temperature | -10 … +55 ºC |
|---|---|
| Storage temperature | -20 … +70 ºC |
| Relative humidity (without condensation) | 5 … 95% |
| Protection class | IP 51 (Front), IP 31 (unmounted) |
| Envelope | Plastic V0 self-extinguishing |
|---|---|
| Fastening | Panel |
| Size (mm) width x height x depth | 144 x 144 x 71 (mm) |
| Electrical safety, Maximum height (m) | 2000 |
|---|
Models and codes
| Code | Model | Description | Measurement Range (V) | Power supply (Vac) | Steps | Switching unit | Quote |
|---|---|---|---|---|---|---|---|
| R13851 | computer SMART III 6 | Power factor controller. Regulation, measurement, leakage control, and communications | 20…300 | 100…520 Vac | 6 | Contactor | Get quote |
| R13862 | computer SMART III 12 | Power factor controller. Regulation, measurement, leakage control, and communications | 20…300 | 100…520 Vac | 12 | Contactor | Get quote |
| R13864 | computer SMART III 14 | Power factor controller. Regulation, measurement, leakage control, and communications | 20…300 | 100…400 Vac | 14 | Contactor | Get quote |
| R13953 | computer SMART III F6-12Vdc | Power factor controller | 100…520 | 100…520 Vac | 6 | EMB-2PH | Get quote |
| R13964 | computer SMART III F12-12Vdc | Power factor controller | 100…520 | 100…520 Vac | 12 | EMB-2PH | Get quote |
| R13951 | computer SMART III Fast 6 | Power factor controller | 100…520 | 100…520 Vac | 6 | EMF / EMB | Get quote |
| R13962 | computer SMART III Fast 12 | Power factor controller | 100…520 | 100…520 Vac | 12 | EMF / EMB | Get quote |