CVM-B: Power analyzer, colour display, panel mounted
Power analyzer, colour display, panel mounted. 2 models, supplied across Saudi Arabia by Volt Solutions.
- Protocol: Modbus RTU, BACnet
- Energy accuracy: 0,5 S (…/5A)
- Communications: RS-485
- Transistor output: 2
- Relays: 2
- Digital inputs: 2
- Input current: …/5 A, …/1 A, …/250 mA
- Mounting: Panel
- 2 models available
Information
The Circutor CVM-B series (power analyzer, colour display, panel mounted) has 2 models. Ordering codes: M56011, M56111. Model names include CVM-B100-ITF-485-ICT2, CVM-B150-ITF-485-ICT2. Volt Solutions supplies it across Saudi Arabia.
The CVM-B100 and CVM-B150 units are panel mounted three-phase power analyzers (dimensions: 96×96 and 144×144 mm, respectively). Both offer 4-quadrant measurement (consumption and generation). Suitable for Medium or Low voltage installations, in both 3 or 4-wire three-phase circuits, two-phase circuits with or without neutral, single-phase circuits or ARON connections.
The CVM-B100 and CVM-B150 high-performance units feature a measurement engine that allows the user to analyse many different electrical parameters, in addition to offering a large variety of optional expansion modules for the same unit.
Features:
- Format: 96×96 (CVM B100) and 144×144 (CVM B150)
- High-resolution VGA colour screen
- IP 65 front panel protection (with sealing joint)
- 5 voltage inputs (3 phases + neutral + earth) 1000 Vf-f
- 4 Current inputs, ITF
- Class 0.2 voltage and current accuracy
- Class 0.5S energy accuracy
- Expandable unit, up to 4 modules, combining digital and analogue outputs, Modbus/TCP, MBus, LonWorks, Profibus, XML/Web
- Modular (optional addition of expansion modules)
- Touch-sensitive movement buttons
- Universal power supply source
- RS485 communications port (Modbus/RTU and BACnet protocols)
- Customisation of parameters to be displayed
- Operating hour indicator for preventive maintenance.
Other features:
- Innovative SCV interface (Slide, Choose & View) for versatile data display, enabling the customisation of the parameters displayed on the screen
- Electrical parameters: instantaneous, maximum, minimum (with date and time) and demand
- Incremental electrical parameters (energy), times, costs, emissions
- 3 Tariffs (can be selected via the digital input or RS485 communications)
- Capable of showing costs and kgCO2 emission sources on the screen, depending on the energy consumed or generated
- 2 Relay outputs for alarms with delay, times, ON and OFF, etc.
- 2 transistor outputs for alarms or impulse generation, with all the possible configuration parameters
- 2 digital inputs, with control over the selection of the unit’s tariffs or configurable for monitoring purposes, with RS-485 Modbus communications, monitoring of logical states of other electromechanical units. (RCCBs, thermal-magnetic circuit breakers, etc.)
Applications
- Control and monitoring of all electrical parameters measured in any electric distribution panel and low and high-voltage connection points.
- 4 alarms (2 per transistor and 2 per relay), fully and independently programmable: low or high value, hysteresis, connection/disconnection delays, normally open or closed standby status and interlocking.
- Generation of impulses with transistor outputs, fully and independently configurable over any incremental parameter (energy, costs, kgCO2, total meter or tariff hours)
- Transducer that converts analogue signals to any instantaneous parameter that the unit can measure or calculate, with built-in expansion modules with analogue outputs.
- Display of process signals, with a built-in expansion module with analogue inputs; optional reporting of these signals to SCADA systems through communication systems
- Control of electrical load or alarm signal operations by programming the transistor or relay outputs that are built-in or added through expansion modules.
- Autonomous datalogger with web server, connected to a M-CVMAB-Datalogger module. Enables direct monitoring of the historical data stored in the unit via a conventional web browser.
400 Hz Applications
CVM-B150 provides a version adapted to 400 Hz networks specially designed for applications such as:
- Aeronautical
- Astronautics
- Naval
- Military
Specifications
| Nominal voltage | 100 … 240 V ~ |
|---|---|
| Frequency | 45 … 65Hz |
| Installation category | CAT III 300 V |
| Nominal voltage | 120 … 300 Vdc |
|---|---|
| Installation category | CAT III 300 V |
| Voltage measuring range | 20…600 V~ |
|---|---|
| Frequency measuring range | 40…70Hz |
| Input impedance | 1.2MΩ |
| Minimum measurement voltage (Vstart) | 10 V~ |
| Installation category | CAT III 600V |
| Maximum input voltage consumption | 0,15VA |
| Nominal current (In) | …/5A, …/1A, …/0.250A |
|---|---|
| Phase current measuring range | 0.01…10A (…/5A),0.01…2A (…/1A), 0.01…0.5A (…/0.250A) |
| Neutral current measuring range | 0.02…0.5A (…/0.250A, calculated) |
| Maximum pulse current | 100 A |
| Minimum current measurement | 0,01 A (…/5A, …/1A, …/0,250A |
| Maximum input current consumption | 0,9 VA |
| Installation category | CAT III 600 V |
| Phase voltage measurement | Class 0.2 ±1 digit (20…600 Vca, …/5A, …/1A, …/0.250A) |
|---|---|
| Neutral voltage measurement | Class 0.5 ±1 digit (50…600 Vca, …/5A, …/1A, …/0.250A) |
| Phase current measurement | class 0,2 ±1 digit 0.05…8A (…/5A),0.01…1.2A ( …/1A), 0,01 … 0,3A (…/0,250A) |
| Neutral current measurement | class 1 ±1 digit 0.05…6A (…/5A),0.05…1.2A ( …/1A), calculated (…/0.250A) |
| Frequency measurement | Class 0.1 (…/5A, …/1A, …/0.250A) |
| Active power measurement (kW) | (Vn 230/110 Vac) class 0.5 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A) |
| Apparent power measurement (kVA) | (Vn 230/110 Vac) class 0.5 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A) |
| Reactive power measurement (kvar) | (Vn 230/110 Vac) Class 1 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A) |
| Active energy measurement (kWh) | (IEC 62053-22) Class 0.5S (…/5A), Class 1 (…/1A), Class 1 (…/0.250A) |
| Reactive energy measurement (kvarh) | (IEC 62053-23) Class 1 (…/5A), Class 2 (…/1A, …/0.250A) |
| Power factor measurement | class 0,5 (…/5A, …/1A, …/0.250A) |
| Voltage THD | class 1 (…/5A, …/1A, …/0.250A) |
| Voltage harmonics (THD) | class 1 (…/5A, …/1A, …/0.250A) |
| Current THD | class 1 (…/5A, …/1A, …/0.250A) |
| Current harmonics (THD) | class 1 (…/5A, …/1A, …/0.250A) |
| Quantity | 2 |
|---|---|
| Type | NPN |
| Maximum voltage | 48 Vdc |
| Maximum current | 130 mA |
| Maximum frequency | 1 kHz |
| Pulse width | 1 ms |
| Pulse output, time period (Ton / Toff) | 0,3 ms/0,7 ms |
| Electrical life (at maximum load) | 3×10 4 cycles |
|---|---|
| Mechanical life | 1×10 7 cycles |
| Maximum switching capacity | 1500 VA |
| Quantity | 2 |
|---|---|
| Type | Potential-free contact |
| Input/output insulation | 4 kV |
| Maximum short-circuit current | 5 mA |
| Maximum open circuit voltage | 15 Vdc |
| Technology / Type | RS-485 / BACnet |
|---|---|
| Protocol | ModBus/RTU, BACnet |
| Display type | TFT color |
|---|---|
| Resolution of the display | VGA (640×480) |
| Display format | 4:3 |
| LED | 3 LED (CPU-Keys-ALARM) |
| Keyboard | Capacitive, 3 keys |
| Working temperature | -10…+60 ºC |
|---|---|
| Storage temperature | -20… +80 ºC |
| Relative humidity (without condensation) | 5 … 95% |
| Protection class | IP 40 (Front), IP 65 (Sealing), IP 30 (unmounted) |
| Envelope | Self-extinguishing V0 plastic |
|---|
| Standards | IEC 61010-1 (1rd. Edition), UNE-EN 61000-6-2, UNE-EN 61000-6-4, IEC 60664-1, IEC 61010-2-030 (First Edition). Measurement according to IEC 61557-12 |
|---|---|
| Certifications | UL 61010-1 3rd edition, CAN/CSA-C22.2 No.61010-1 3rd. edition 2012-05 |
| Electrical safety, Maximum height (m) | 2000 |