CVM-C4: Power analyzer, panel mounted 96x96
Manufactured by Circutor

CVM-C4: Power analyzer, panel mounted 96×96

Power analyzer, panel mounted 96×96. 1 model, supplied across Saudi Arabia by Volt Solutions.

  • Protocol: Modbus RTU
  • Communications: RS-485
  • Transistor output: 2
  • Relays: 2
  • Digital inputs: 2
  • Measuring current Channels: 3
  • Input current: …/5 A, …/1 A
  • Mounting: Panel

Information

The Circutor CVM-C4 series (power analyzer, panel mounted 96×96) has 1 model. Ordering code: M52706. Volt Solutions supplies it across Saudi Arabia.

CVM-C4 is a power analyser that measures, calculates and displays the main electrical parameters for single-phase and three-phase networks (with or without neutral) on its screen. Measurement is made in true rms value, by means of 3 AC voltage inputs and 3 /5 A or /1 A current inputs. Relay outputs enable local operation in the event of an alarm event being triggered. Its dimensions are 96 x 96 mm with a depth of only 41.5 mm. Current measurement is indirectly carried out by /5A or /1A transformers. It allows AC (80…270 Vac)and DC (80…270 Vdc or 18… 36 Vdc power supply systems). It features RS-485 communications enabling remote data readout or Scada or Master centralisation.

Applications

  • For electrical parameter measurement in areas whose reduced dimensions require the installation of a space-saving panel analyser.
  • Instantaneous value measurement of electrical parameters with communications.
  • Logging of consumed or generated Active or Reactive Energy.
  • The device’s relay outputs allow the installation to be locally operated.
  • Programmable alarms by setting relay activation time, connection delay and hysteresis.
  • 5000 imp/kWh energy impulse outputs
  • Energy measurement of two different sources on 2 separate meters (by digital input activation).
  • Voltage and current THD% measurement to check for harmonics in the installation.

Specifications

AC power supply
Nominal voltage80 … 270 Vac
Frequency50/60 Hz
Consumption6 … 18 VA
Installation categoryCAT III 300 V
DC power supply
Nominal voltage80…270 Vdc
Consumption1.5 … 1.8 W
Installation categoryCAT III 300 V
Voltage measurement circuit
Nominal voltage100…277 V~ Ph-N (± 8%)
Frequency measuring range45…65 Hz
Input impedance> 1.7 MΩ
Minimum measurement voltage (Vstart)10 V
Maximum permanent measurement voltage1.2 Un continuous, 2 Un instantaneous (1 min)
Consumption< 0.2 VA (por fase)
Installation categoryCAT III 300 V
Sampling frequency45…65 Hz
Current measurement circuit
Nominal current (In)1 A / 5 A ~
Allowable overload1.2 In continuous, 10 In instantaneous(5s)
Consumption< 0.2 VA (por fase)
Installation categoryCAT III 300 V
Measurement accuracy
Phase voltage measurement0.2 %
Phase current measurement0.2 %
Frequency measurement0.5 %
Active power measurement (kW)0.5 %
Reactive power measurement (kvar)0.5 %
Active energy measurement (kWh)0.5 %
Reactive energy measurement (kvarh)0.5 %
Power factor measurement0.5 %
Digital transistor outputs
TypePassive impulse
Maximum voltage27 Vcc
Maximum current27 mA
Maximum frequency10 Hz
Pulse widthMinimum pulse width: 80mA
Digital relay outputs
TypeRelay
Quantity2
Maximum open contact voltage277 V ~ / 30 Vdc
Maximum current5 A ~
Resistive load (max.)250 Vca / 5 Aca, 30 Vcc / 5 Acc
Electrical life(250 V ~ / 5 A) 1 x 10 5
Maximum switching capacity1385 VA / 150 W
Digital inputs
Quantity2
TypePotential-free contact
Input/output insulation3,75 kV RMS
Maximum short-circuit current4 mA
Maximum open circuit voltage30 V
Serial communication
Technology / TypeRS-485
User interface
Display typeLCD
Keyboard3 keys
Environmental characteristics
Working temperature-10 … +60 ºC
Storage temperature-20 … +70 ºC
Relative humidity (without condensation)5 … 95%
Protection classFront: IP54, Rear: IP20
Mechanical characteristics
EnvelopePolycarbonate + ABS
Weight (kg)0,268
Size (mm) width x height x depth96 x 96 x 41.5 (mm)
Standards
StandardsIEC 61010-1, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11
Electrical safety, Installation categoryCAT III 300 V
Electrical safety, Contamination level/classPollution resistance 2
Electrical safety, Maximum height (m)2000

Models and codes

CodeModel ProtocolCommunicationsTransistor outputRelays Quote
M52706 CVM-C4-ITF-485-ICT2 Modbus RTURS-48522 Get quote