CVM-C4: Power analyzer, panel mounted 96×96
Power analyzer, panel mounted 96×96. 1 model, supplied across Saudi Arabia by Volt Solutions.
- Protocol: Modbus RTU
- Communications: RS-485
- Transistor output: 2
- Relays: 2
- Digital inputs: 2
- Measuring current Channels: 3
- Input current: …/5 A, …/1 A
- Mounting: Panel
Information
The Circutor CVM-C4 series (power analyzer, panel mounted 96×96) has 1 model. Ordering code: M52706. Volt Solutions supplies it across Saudi Arabia.
CVM-C4 is a power analyser that measures, calculates and displays the main electrical parameters for single-phase and three-phase networks (with or without neutral) on its screen. Measurement is made in true rms value, by means of 3 AC voltage inputs and 3 /5 A or /1 A current inputs. Relay outputs enable local operation in the event of an alarm event being triggered. Its dimensions are 96 x 96 mm with a depth of only 41.5 mm. Current measurement is indirectly carried out by /5A or /1A transformers. It allows AC (80…270 Vac)and DC (80…270 Vdc or 18… 36 Vdc power supply systems). It features RS-485 communications enabling remote data readout or Scada or Master centralisation.
Applications
- For electrical parameter measurement in areas whose reduced dimensions require the installation of a space-saving panel analyser.
- Instantaneous value measurement of electrical parameters with communications.
- Logging of consumed or generated Active or Reactive Energy.
- The device’s relay outputs allow the installation to be locally operated.
- Programmable alarms by setting relay activation time, connection delay and hysteresis.
- 5000 imp/kWh energy impulse outputs
- Energy measurement of two different sources on 2 separate meters (by digital input activation).
- Voltage and current THD% measurement to check for harmonics in the installation.
Specifications
| Nominal voltage | 80 … 270 Vac |
|---|---|
| Frequency | 50/60 Hz |
| Consumption | 6 … 18 VA |
| Installation category | CAT III 300 V |
| Nominal voltage | 80…270 Vdc |
|---|---|
| Consumption | 1.5 … 1.8 W |
| Installation category | CAT III 300 V |
| Nominal voltage | 100…277 V~ Ph-N (± 8%) |
|---|---|
| Frequency measuring range | 45…65 Hz |
| Input impedance | > 1.7 MΩ |
| Minimum measurement voltage (Vstart) | 10 V |
| Maximum permanent measurement voltage | 1.2 Un continuous, 2 Un instantaneous (1 min) |
| Consumption | < 0.2 VA (por fase) |
| Installation category | CAT III 300 V |
| Sampling frequency | 45…65 Hz |
| Nominal current (In) | 1 A / 5 A ~ |
|---|---|
| Allowable overload | 1.2 In continuous, 10 In instantaneous(5s) |
| Consumption | < 0.2 VA (por fase) |
| Installation category | CAT III 300 V |
| Phase voltage measurement | 0.2 % |
|---|---|
| Phase current measurement | 0.2 % |
| Frequency measurement | 0.5 % |
| Active power measurement (kW) | 0.5 % |
| Reactive power measurement (kvar) | 0.5 % |
| Active energy measurement (kWh) | 0.5 % |
| Reactive energy measurement (kvarh) | 0.5 % |
| Power factor measurement | 0.5 % |
| Type | Passive impulse |
|---|---|
| Maximum voltage | 27 Vcc |
| Maximum current | 27 mA |
| Maximum frequency | 10 Hz |
| Pulse width | Minimum pulse width: 80mA |
| Type | Relay |
|---|---|
| Quantity | 2 |
| Maximum open contact voltage | 277 V ~ / 30 Vdc |
| Maximum current | 5 A ~ |
| Resistive load (max.) | 250 Vca / 5 Aca, 30 Vcc / 5 Acc |
| Electrical life | (250 V ~ / 5 A) 1 x 10 5 |
| Maximum switching capacity | 1385 VA / 150 W |
| Quantity | 2 |
|---|---|
| Type | Potential-free contact |
| Input/output insulation | 3,75 kV RMS |
| Maximum short-circuit current | 4 mA |
| Maximum open circuit voltage | 30 V |
| Technology / Type | RS-485 |
|---|
| Display type | LCD |
|---|---|
| Keyboard | 3 keys |
| Working temperature | -10 … +60 ºC |
|---|---|
| Storage temperature | -20 … +70 ºC |
| Relative humidity (without condensation) | 5 … 95% |
| Protection class | Front: IP54, Rear: IP20 |
| Envelope | Polycarbonate + ABS |
|---|---|
| Weight (kg) | 0,268 |
| Size (mm) width x height x depth | 96 x 96 x 41.5 (mm) |
| Standards | IEC 61010-1, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11 |
|---|---|
| Electrical safety, Installation category | CAT III 300 V |
| Electrical safety, Contamination level/class | Pollution resistance 2 |
| Electrical safety, Maximum height (m) | 2000 |
Models and codes
| Code | Model | Protocol | Communications | Transistor output | Relays | Quote |
|---|---|---|---|---|---|---|
| M52706 | CVM-C4-ITF-485-ICT2 | Modbus RTU | RS-485 | 2 | 2 | Get quote |