CVM-D400: Fixed power analyzer
Manufactured by Circutor

CVM-D400: Fixed power analyzer

2/6 or 4/12 single-phase and/or three-phase network analysers with memory, DIN rail. 6 models, supplied across Saudi Arabia by Volt Solutions.

  • Protocol: Modbus TCP/IP , Modbus RTU
  • Memory: Yes
  • Harmonics: 15
  • Mounting: DIN rail
  • Communications: Wi-Fi, Ethernet, RS-485, RS-486, RS-487
  • Transistor output: 2, 4
  • 6 models available

Information

The Circutor CVM-D400 series (fixed power analyzer) has 6 models. Ordering codes: M551A2, M55132, M551A4, M55134, M55136, M55138. Model names include CVM-D420-MC, CVM-D421-SCV, CVM-D440-MC. Volt Solutions supplies it across Saudi Arabia.

The CVM-D400 series are multi-channel power analysers designed for reading multiple loads or circuits (Branch Circuit Monitoring). These devices can manage up to 12 single-phase or 4 three-phase lines or loads, or any combination of them in a single device. They also allow each type of consumption to be labelled, grouping together the total consumption of all the loads destined for the same purpose without the need for any type of programming. The results are automatically displayed on screen or via communications. The devices are configured via an integrated web interface, accessible via Wi-Fi or Ethernet, or directly from the MyConfig App. Both options allow the connection to be checked and modified via the ‘autowiring’ option, avoiding wiring errors and saving time during commissioning.

Applications

  • Measurement of electrical parameters in multi-channel installations, such as data processing centres and switchboards of single-phase loads.
  • Simultaneous measurement at 4 different points in three-phase installations
  • Its compact size is perfect for assembly on electric panels.

Specifications

Voltage measurement circuit
Voltage measuring range120… 300 V~Ph-N / 120 … 520 V ~ph-ph
Frequency measuring range45…65 Hz
Input impedance0,4 MΩ
Minimum measurement voltage (Vstart)120 V ~
Installation categoryCAT III 300 V
Sampling frequency45…65 Hz
Maximum input voltage consumption5…8 VA
Current measurement circuit
Installation categoryCAT III 300 V
Measurement accuracy
Phase voltage measurement0,5%
Active power measurement (kW)1%
Active energy measurement (kWh)1%
Digital transistor outputs
TypeNPN
Maximum voltage24 Vdc
Maximum current50 mA
Maximum frequency5 imp/s
Pulse width30 … 500 ms
Wireless communication
Technology / TypeWi-Fi
Band2,4 GHz (2,4…2,5 GHz)
Serial communication
Technology / TypeRS-485
ProtocolModbus RTU
Communication Network
Technology / InterfaceEthernet 10BaseT – 100BaseTX
ProtocolModbus TCP – Web server – Web socket
Connection modeDHCP ON/OFF
Connection mechanismRJ-45
User interface
Display typeLCD
LED2 LED
Keyboard3 keys
Environmental characteristics
Working temperature-10 ºC… +60 ºC
Storage temperature10 ºC… +75 ºC
Relative humidity (without condensation)5 … 95%
Mechanical characteristics
EnvelopeSelf-extinguishing V0 plastic
FasteningDIN rail
Size (mm) width x height x depth105 x 104 x 72 (mm)
Standards
StandardsUNE-EN 61000-4-4, UNE-EN 61000-4-5, UNE-EN 61000-4-11,UNE-EN 61000-6-3, UNE-EN 61000-6-1, UNE-EN 61010-1, UNE-EN 60068-2-1, UNE-EN 60068-2-2,UNE-EN 60068-2-78, IEC 61010-2-030, IEC 61326-1, UNE-EN 61000-4-20, ETSI EN 301 489-1 V2.2.3, ETSI EN 301 489-17 V3.2.4
Electrical safety, Installation categoryCAT III 300 V
Electrical safety, Contamination level/classPollution resistance 2
Electrical safety, Maximum height (m)2000

Models and codes

CodeModel CommunicationsTransistor outputInput currentNª Input channelsClamp Quote
M551A2 CVM-D420-MC Wi-Fi | Ethernet | RS-4852…/250 mA1…2(III) | 1…6(II)– Get quote
M55132 CVM-D421-SCV Wi-Fi | Ethernet | RS-4852…/333 mV1…2(III) | 1…6(II)– Get quote
M551A4 CVM-D440-MC Wi-Fi | Ethernet | RS-4854…/250 mA1…4(III) | 1…12(II)– Get quote
M55134 CVM-D441-SCV Wi-Fi | Ethernet | RS-4854…/333 mV1…4(III) | 1…12(II)– Get quote
M55136 kit CVM-D421+2xSCV1 Wi-Fi | Ethernet | RS-4862…/333 mV1…2(III) | 1…6(II)6 Get quote
M55138 kit CVM-D441+4xSCV1 Wi-Fi | Ethernet | RS-4874…/333 mV1…4(III) | 1…12(II)12 Get quote

Downloads

Support from our engineers