Manufactured by Circutor
CVM-D41 DC: DC power analyzer
DC power analyzer. 2 models, supplied across Saudi Arabia by Volt Solutions.
- Protocol: Modbus RTU
- Módules: 6
- IP: 54
- Communications: RS-485
- Relays: 2
- Digital inputs: 2
- Analog output: 1 (20 mA)
- System: DC (Shunt)
- 2 models available
Information
The Circutor CVM-D41 DC series (DC power analyzer) has 2 models. Ordering codes: M56638, M566380040000. Volt Solutions supplies it across Saudi Arabia.
The CVM-D41 DC is a digital power analyzer for installing on a DIN rail. Its screens are operated using buttons to display different electrical parameters in a DC network of up to 1500 VDC, such as voltage, current, power and energy (A·h).
This analyzer has the following key features:
- DIN rail installation.
- DC voltage measurement up to 1500VDC CATIIII
- Shunt current measurement
- 2 digital inputs + 2 relay outputs + 1 analogue output (0/4…20 mA) or (0 / 2 … 10 Vdc), depending on the model
- LED status indicator
- RS-485 communications (Modbus/RTU)
- Configuration via Power Studio SCADA
Applications
Measurement and management of installations with a DC power supply:
- Industrial Applications
- Electric vehicle charging points
- Self-supply systems
- Solar photovoltaic Installations
- HVAC
- Industrial process control
Specifications
| Installation category | CAT III 300V |
|---|
| Installation category | CAT III 300 V |
|---|
| Nominal voltage | ± 150 / 300 / 600 / 1000 / 1500 Vdc |
|---|---|
| Maximum permanent measurement voltage | 1.2 Un continuous |
| Consumption | < 1 VA |
| Installation category | CAT III 1500 V |
| Nominal current (In) | Shunt: 50 / 60 /75 / 100 / 150 / 200 / 250 / 300 / 400 / 600 mV |
|---|---|
| Allowable overload | 1.2 In continuous (max.1500 Vdc) |
| Consumption | < 1 VA |
| Installation category | CAT III 1500 V |
| Phase voltage measurement | Class 0.5 |
|---|---|
| Phase current measurement | Class 0.5 |
| Active power measurement (kW) | Class 1 |
| Active energy measurement (kWh) | Class 1 |
| Quantity | 2 |
|---|---|
| Maximum current | 2.5 A |
| Electrical life | 1 x 10 5 (250 V~ / 5A) |
| Maximum switching capacity | 625 VA |
| Quantity | 2 |
|---|---|
| Type | Potential-free contact |
| Input/output insulation | 4000 V ~ |
| Maximum short-circuit current | 3.3 mA dc |
| Maximum open circuit voltage | 17 V dc |
| Quantity | 1 |
|---|---|
| Maximum internal voltage | 17 V dc |
| Linearity | 0.5 % |
| Current mode, nominal range | 0 … 20 mA, 4 … 20 mA, 4-12-20 mA |
| Current mode: maximum load resistance | 350 Ω |
| Technology / Type | RS-485 |
|---|---|
| Protocol | ModBus RTU |
| Display type | LCD 5 digits |
|---|---|
| Keyboard | 4 keys |
| Working temperature | -25 … +70 ºC |
|---|---|
| Storage temperature | -25 … +70 ºC |
| Relative humidity (without condensation) | ≤ 93 % |
| Protection class | Front: IP54, Rear: IP20 |
| Envelope | PC + ABS |
|---|---|
| Fastening | DIN rail |
| Weight (kg) | 0,7 |
| Size (mm) width x height x depth | 108 x 117.43 x 74 (mm) |
| Standards | IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61010-1, IEC 61326-1, IEC 61010-2-030 |
|---|---|
| Electrical safety, Contamination level/class | Pollution resistance 2 |
| Electrical safety, Maximum height (m) | 2000 |