CVM-D50: Din rail three-phase power analyser with memory
Din rail three-phase power analyser with memory. 3 models, supplied across Saudi Arabia by Volt Solutions.
- Protocol: Modbus TCP/IP
- Memory: Yes
- Communications: Ethernet, Wi-Fi
- Harmonics: 31
- Power supply: 90…264 Vac/Vdc
- Mounting: DIN rail
- 3 models available
Information
The Circutor CVM-D50 series (din rail three-phase power analyser with memory) has 3 models. Ordering codes: M56570, M56580, M56590. Model names include CVM-D50-ITF, CVM-D50-MC, CVM-D50-FLEX. Volt Solutions supplies it across Saudi Arabia.
Three-phase power analyzer (balanced and unbalanced) for assembly on DIN rail, very small, with 4-quadrant measurements and integrated memory for data logging. Main features include: • Current measurement (depending on model) …/5 or…/1 A or…/250 mA or Rogowski-type sensors. • Wi-Fi and Ethernet communications (Modbus TCP/IP). • Integrated memory. • With web Server to view, configure and download data. • Compatible with the MyConfig app. • Sealable with terminal cover. • Display of THD% and up to the 31st harmonic (V, A). • DIN rail format just 3 modules wide. • High-contrast backlit display. • 72 x 72 mm panel mount with front adapter. • Includes an operating-hours and working-hours counter for CAE.
Applications
• Control application in distribution panels and low- and medium-voltage connections where an analyzer has to be installed on the DIN rail due to space constraints.
• Alarm control: Maximum value, minimum, delay and programmable interlocking.
• Logging of active or capacitive and inductive reactive energy.
• Capture and storage of instantaneous, maximum and minimum data of the electrical parameters measured.
Specifications
| Nominal voltage | 100 … 240 V~ ± 10 % |
|---|---|
| Frequency | 50…60 Hz |
| Installation category | CAT III 300 V |
| Nominal voltage | 100 … 240 Vd.c. ± 10 % |
|---|---|
| Consumption | 1,8 … 2 W |
| Nominal voltage | 230V Ph-N, 400V Ph-Ph |
|---|---|
| Frequency measuring range | 45…65 Hz |
| Input impedance | 400 kΩ |
| Minimum measurement voltage (Vstart) | 11,5 V Ph-N |
| Installation category | CAT III 300 V |
| Maximum input current consumption | 0,9 VA |
|---|---|
| Installation category | CAT III 300 V |
| Phase voltage measurement | 0.5% ± 1 digit (5 … 120 % Un) |
|---|---|
| Frequency measurement | 0,50% |
| Technology / Type | Wi-Fi, IEEE 802.11 b/g, IEEE 802.11 n (Up 150 Mbps) |
|---|---|
| Band | Wi-Fi (2.4 … 2.5 GHz.) |
| Technology / Interface | Ethernet |
|---|---|
| Protocol | Modbus TCP – Web server |
| Display type | LCD Custom COG |
|---|---|
| Keyboard | 3 keys |
| Working temperature | -10 … +50 ºC |
|---|---|
| Storage temperature | -30 … +80 ºC |
| Relative humidity (without condensation) | 5…95% |
| Protection class | IP 30 / Front: IP 40, IK08 |
| Envelope | Self-extinguishing V0 plastic |
|---|---|
| Fastening | DIN rail |
| Size (mm) width x height x depth | 52.5 x 118 x 74 (mm) |
| Standards | IEC/EN 61010-1; IEC/EN 61010-2-030; UNE-EN 55016-2-1; UNE-EN 61000-4-2; UNE-EN 61000-4-20; UNE-EN 61000-4-4; UNE-EN 61000-4-5; UNE-EN 61000-4-6; UNE-EN 61000-4-8; UNE-EN IEC 61000-4-11; UNE-EN 61000-4-3; ETSI-EN 301 489-1 Ver. 2.1.1; ETSI-EN 301 489-17 Ver. 3.1.1; UNE-EN 60068-2-1; UNE-EN 60068-2-2:2008; UNE-EN 60068-2-78; IEC 61557-12; EN 18031-1 |
|---|---|
| Electrical safety, Contamination level/class | 2 |
| Electrical safety, Maximum height (m) | 2000 |