CVM-E3-MINI: DIN rail three-phase power analyzer,
Manufactured by Circutor

CVM-E3-MINI: DIN rail three-phase power analyzer,

DIN rail three-phase power analyzer,. 6 models, supplied across Saudi Arabia by Volt Solutions.

  • Harmonics: 31
  • Mounting: DIN rail
  • Protocol: Modbus RTU, BACnet, Modbus TCP/IP
  • Communications: RS-485, Ethernet, Wi-Fi
  • Power supply (Vac): 207…253 Vac, 90…264 Vac/Vdc
  • Input current: …/5 A, …/1 A, …/250 mA, Rogowski
  • 6 models available

Information

The Circutor CVM-E3-MINI series (DIN rail three-phase power analyzer) has 6 models. Ordering codes: M56414, M56424, M56454, M56470, M56480, M56490. Model names include CVM-E3-MINI-ITF-485-IC, CVM-E3-MINI-MC-485-IC, CVM-E3-MINI-FLEX-485-IC. Volt Solutions supplies it across Saudi Arabia.

Three-phase power analyzer (balanced and unbalanced) for mounting on DIN rail, very compact, with measurements in 4 quadrants.

Other features:

  • Current measurement …/5 or …/1 A or …/250 mA or Rogowski type sensors
  • With ITF technology: ITF galvanic insulation protection
  • DIN rail with only 3 modules
  • High-contrast backlit display
  • 72 x 72 mm panel mounting with front adapter
  • RS-485 communication (Modbus/RTU up to 19.2 kbps) (Bacnet up to 19.2 kbps)
  • One transistor output (programmable)
  • One digital input for selecting tariff or logic states
  • Sealable terminal cover
  • Harmonic display (V, A) up to 31º

Applications

  • Control application in low- and medium-voltage distribution panels and switchboards where it is necessary to place an analyzer on the DIN rail due to problems of space.
  • Alarm control. Maximum value, minimum value and programmable delay.
  • Control of active or reactive energy by impulse output.
  • Capture of maximum and minimum instantaneous data of electrical parameters measured.

Specifications

AC power supply
Nominal voltage207…253 Vc.a.
Frequency50…60 Hz
Installation categoryCAT III 300 V
Voltage measurement circuit
Nominal voltage300V Ph-N, 520V Ph-Ph
Frequency measuring range45…65 Hz
Input impedance400 kΩ
Minimum measurement voltage (Vstart)11 V Ph-N
Installation categoryCAT III 300 V
Current measurement circuit
Maximum input current consumption0,9 VA
Installation categoryCAT III 300 V
Measurement accuracy
Phase voltage measurement0.5% ± 1 digit
Phase current measurement0,5% ± 1 digit
User interface
Display typeLCD Custom COG
LED2 LED
Keyboard3 keys
Environmental characteristics
Relative humidity (without condensation)5…95%
Protection classIP 30 / Front: IP 40
Mechanical characteristics
EnvelopeSelf-extinguishing V0 plastic
FasteningDIN rail
Size (mm) width x height x depth52.5 x 118 x 74 (mm)
Standards
StandardsIEC 61010-1, IEC 61010-2-030, IEC 61326-1, IEC 61557-12 , UL94
Electrical safety, Maximum height (m)2000

Models and codes

CodeModel ProtocolCommunicationsTransistor outputDigital inputsPower supply (Vac)Input current Quote
M56414 CVM-E3-MINI-ITF-485-IC Modbus RTU | BACnetRS-48511207…253 Vac…/5 A | …/1 A Get quote
M56424 CVM-E3-MINI-MC-485-IC Modbus RTU | BACnetRS-48511207…253 Vac…/250 mA Get quote
M56454 CVM-E3-MINI-FLEX-485-IC Modbus RTU | BACnetRS-48511207…253 VacRogowski Get quote
M56470 CVM-E3-MINI-ITF-WiEth Modbus TCP/IPEthernet | Wi-Fi––90…264 Vac/Vdc…/5 A | …/1 A Get quote
M56480 CVM-E3-MINI-MC-WiEth Modbus TCP/IPEthernet | Wi-Fi––90…264 Vac/Vdc…/250 mA Get quote
M56490 CVM-E3-MINI-FLEX-WiEth Modbus TCP/IPEthernet | Wi-Fi––90…264 Vac/VdcRogowski Get quote