Line-CVM-D: Power analyzer, Line series
Manufactured by Circutor

Line-CVM-D: Power analyzer, Line series

Power analyzer, Line series. 1 model, supplied across Saudi Arabia by Volt Solutions.

  • Protocol: Modbus RTU
  • Communications: RS-485, Bus-Line
  • Transistor output: 2
  • Measuring current Channels: 3
  • Harmonics: 40
  • Input current: …/5 A, …/1 A, …/250 mA
  • Mounting: DIN rail

Information

The Circutor Line-CVM-D series (power analyzer, Line series) has 1 model. Ordering code: M58100. Volt Solutions supplies it across Saudi Arabia.

The Line-CVM-D32 is a power analyser that measures, calculates and displays the main electrical parameters in single-phase networks, in systems with two phases without ground, with ARON connections or balanced or unbalanced three-phase systems. The measurement is a true RMS that relies on 3 AC voltage inputs and 3 current inputs. The device is modular and scalar thanks to expansion modules with different functionalities. The current is measured indirectly using /5A, /1A or /250mA transformers The voltage is measured directly in networks of up to 300V ~ P-N or through voltage transformers. Supply quality events counter (Overvoltages, gaps and interruptions)

Applications

  • Measurement of electrical parameters in switchboards and low- and medium-voltage connections where space constraints require installing a space-saving analyser in the DIN rail.
  • Measurement of instantaneous, maximum and minimum values of electrical parameters.
  • Logging of consumed or generated Active or Reactive Energy.
  • Pricing of electricity in up to 4 tariffs (via communications or expansion module inputs)
  • Generation of impulses through outputs to a transistor, fully and independently configurable based on any incremental parameter of active or reactive energy, either per total counter or per tariff.
  • The installation can be controlled by way of programmable timer on delay, timer off delay and interlock alarms.
  • Ability to expand the analyser’s features by using expansion modules with transistor, relay or analogue inputs/outputs.
  • Convert any instantaneous parameter measured or calculated by the device into analogue signals by incorporating analogue output expansion modules.
  • Track the status of components in the installation by using the status of the inputs to the expansion module.

Specifications

AC power supply
Nominal voltage80 … 264 V ~
Frequency50 … 60 Hz
Consumption3 … 8 VA
Installation categoryCAT III 300 V
DC power supply
Nominal voltage100 … 300 Vdc
Consumption2 … 3 W
Installation categoryCAT III 300 V
Voltage measurement circuit
Nominal voltage300 V Ph-N / 520 V Ph-Ph
Voltage measuring range20…300 V~
Frequency measuring range47 … 63 Hz
Input impedance1 MΩ
Minimum measurement voltage (Vstart)10 V ac
Installation categoryCAT III 300 V
Current measurement circuit
Nominal current (In)…/5 A, …/1 A, …/0.250A (transformers type MC)
Phase current measuring range(In: …/5 A): 0.01 … 10 A(In: …/1 A): 0.01 … 2 A(In: …/0.250 A): 0.01 … 0.5 A
Maximum pulse current100 A (< 1s)
Minimum current measurement0.01 A
Maximum input current consumption0.9 VA
Installation categoryCAT III 300 V
Measurement accuracy
Phase voltage measurement…/5A, …/1A, …/0.250A (Class 0.2 % for three-phase and phase values)
Phase current measurement…/5A, …/1A (class 0.2 % for three-phase and phase values), … / 0.250 A (class 1 % for I ≥ 20 % In, for three-phase and phase values)
Frequency measurement…/5A (Class 0.1 % for three-phase and phase values), Class 0.1 % ( …/1A, …/0.250A)
Active power measurement (kW)…/5A (Class 0.5 % for three-phase and phase values), …/1A (Class 1 % for I ≥ 5 % In), … / 0.250 A (Class 1 % for I ≥ 20 % In)
Apparent power measurement (kVA)…/5A (Class 0.5 % for three-phase and phase values), …/1A (Class 1 % for I ≥ 5 % In), … / 0.250 A (Class 1 % for I ≥ 20 % In)
Reactive power measurement (kvar)…/5A (class 1 % for three-phase and phase values), …/1A (class 1 %), …/0.250A (class 2 %)
Active energy measurement (kWh)Class 0.5S (…/5A), Class 1 (…/1A), Class 1 (…/0.250A)
Reactive energy measurement (kvarh)Class 1 (…/5A), Class 2 (…/1A, …/0.250A)
Power factor measurement…/5A (class 0.5 % for three-phase and phase values), class 0.5 % ( …/1A, … /0.250A)
Digital transistor outputs
Quantity2
TypeOptocoupler NO
Maximum voltage48 Vcc
Maximum current120 mA
Maximum frequency500 Hz
Pulse width1 ms
Serial communication
Technology / TypeRS-485, Bus-Line
User interface
Display typeTFT RGB 1.77" 160×128 pixel
LED2 LED
Keyboard3 keys
Environmental characteristics
Working temperature-10 … +50 ºC
Storage temperature-20 … +70 ºC
Relative humidity (without condensation)5 … 95%
Protection classIP30, Front: IP40
Mechanical characteristics
EnvelopeSelf-extinguishing V0 plastic
FasteningDIN rail (IEC 60715)
Weight (kg)0,228
Size (mm) width x height x depth52.5 x 118 x 70 (mm)
Standards
StandardsUNE-EN 61010-1, UNE-EN 61010-2-30, UNE-EN 61326-1
CertificationsUL 61010-1
Electrical safety, Maximum height (m)2000

Models and codes

CodeModel ProtocolCommunicationsTransistor outputMeasuring current Channels Quote
M58100 Line-CVM-D32 Modbus RTURS-485 | Bus-Line23 Get quote

Downloads